Description
Compatibility Designed to comply with the requirements of BS5839-4 (for head-out monitoring use 1 x BF378M module on the EFP1’s zone circuit).
Mains supply 230V 50/60Hz.
Internal power supply 27V nominal.
Total output current limited to 400mA @ 230V.
Quiescent current 40mA (with no mains supply, detector and sounder EOLs fitted, no other loads supplied by panel).
Max battery size and type 2 x 12V 2.3Ah VRLA connected in series.
No. of detector zone circuits 1 (Max. length per circuit is 500m).
Call point resistor value 470 to 680Ω.
Max. devices per detector zone 20 detectors (max. detector current 2mA). No limit for manual call points.
No. of conventional sounder circuits 2 (Max. length per circuit is 500m).
EOL resistor value 6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Max. sounder output current 400mA (to all outputs). Outputs are fused at 400mA.
Open collector outputs Available via optional expansion loom FF380X.
Auxiliary inputs Available via optional expansion loom FF380X.
Indicators Mains on; Zone Fire; Zone Fault; Sounder Fault; Battery/PSU Fault; O/C Zone Fault; S/C Zone Fault.
Controls External (keyswitch activated): Reset; Silence Alarm/Fault Sounders; Evacuate. Internal: Revert to S/C equals Fire.
Product dimensions (mm) 271 W x 200 H x D 70mm.
Construction & finish Metal lid and base.
IP Rating IP30.
Weight 2.3kg.
Operating conditions/temperature -5ºC to +40ºC. Max relative humidity: 95%.
Reviews